Addressable Control Modules |
|
|
|
|
Jan 22, 2005 at 10:09 AM |
|
Addressable control modules interface the serial line circuit
(SLC) with other equipment allowing the fire alarm control panel
additional control relay or output circuits. In the first diagram
below a relay type module is interface with the SLC. The second
diagram is a output circuit.
The
M500R Relay Control Module is intended for use in intelligent, two-wire
systems, where the individual address of each module is selected
using the built-in rotary decade switches. It allows a compatible
control panel to switch discrete contacts by code command. The
relay contains two isolated sets of Form-C contacts, which
operate as a DPDT switch and are rated in accordance with the table in
the manual. Circuit connections to the relay contacts are not
supervised by the module. The module also has a panel controlled
LED indicator. This module can be used to replace an M500C module
that has been configured for Form-C operation.
Download Data Sheet
M500S Supervised Control Modules are intended for use in intelligent,
two-wire systems, where the individual address of each module is
selected using the built-in rotary decade switches. This module
is used to switch an external power supply, which can be a DC
power supply or an audio amplifier (up to 80 VRMS), to
notification appliances. It also supervises the wiring to the connected
loads and reports their status to the panel as NORMAL, OPEN, or
SHORT CIRCUIT. The M500S has two pairs of output termination
points available for fault-tolerant wiring and a panelcontrolled LED
indicator. This module can be used to replace an M500C module
that has been configured for supervised wiring operation.