Secutron MRI-M500 series modules |
|
|
|
|
Feb 05, 2005 at 10:52 AM |
|
Secutron's
intelligent module products are designed to meet a wide range of
applications. Monitor and control modules can be used to supervise and
activate sounders, strobes, door closers, pull stations, waterflow
switches, conventional smoke detectors, and more. Each module is
rigorously designed and tested for electromagnetic compatibility and
environmental reliability, in many cases exceeding industry standards.
Modules are addressed with easy-to-use rotary code switches. Full size
modules mount in standard 4" x 4" x 2-18" junction box. Wiring
terminals are easily accessible for troubleshooting purposes.
Secutrons monitor modules provide an interface to contact devices, such
as security contacts, waterflow switches, or pull stations. They are
capable of Styles A and B supervised wiring to the load device
(MRIM500MB is capable of Style D). Conventional 4- wire smoke detectors
can be monitored through their alarm and trouble contacts, wired as an
initiating loop to the module. In addition to transmitting the
supervised state of the monitored device (normal, open, or short), the
full analog supervision measurement is sent back to the panel. This
allows impedance changes in the supervised loop to the monitored device
to be detected. The MRI-M500DM is capable of monitoring two separate
Class B circuits simultaneously, making it ideal for waterflow tamper
switch and flow switch monitoring. The small size of the MRI-M501M
allows it to fit inside devices or junction boxes behind devices.
The MRI-M500X Isolator Module is an automatic switch that opens when
the line voltage drops below four volts. Isolator modules should be
spaced between groups of sensors or modules in a loop to protect the
rest of the loop. If a short occurs between any two isolators, then
both isolators immediately switch to an open circuit state and isolate
the devices between them. The remaining units on the loop continue to
fully operate. No more than 25 devices are recommended for each group.
The MRI-M502M Zone Interface Module allows intelligent panels to
interface and monitor two-wire conventional smoke detectors. All
two-wire detectors being monitored must be UL or ULC compatible with
the module. The MRI-M502M is addressed through the communication line
of an intelligent system. It transmits the status of one zone of
two-wire detectors to the fire alarm control panel. Status conditions
are reported as normal, open, or alarm. The interface module supervises
the zone of detectors and the connection of the external power supply.
MRI-M500R Relay Module The MRI-M500R Relay Module contains two isolated
sets of Form-C contacts, which operate as a DPDT switch. The module
allows the control panel to switch these contacts on command. No
supervision is provided for the notification appliance circuit.
|