Potter VSR-F Sprinkler Flow Switch |
|
|
|
|
Jan 29, 2005 at 01:14 PM |
|
The
Model VSR-F is a vane type waterflow switch for use on wet sprinkler
systems. It is UL Listed and FM Approved for use on steel pipe;
schedules 10 through 40, sizes 2" thru 8" (50mm thru 200mm).
LPC approved sizes are 2" thru 8" (50mm thru 200mm). The unit may also
be used as a sectional waterflow detector on large systems.
The unit contains two single pole, double throw, snap action switches
and an adjustable, instantly recycling pneumatic retard. The switches
are actuated when a flow of 10 gallons per minute (38 LPM) or more
occurs downstream of the device. The flow condition must exist for a
period of time necessary to overcome the selected retard period.
ENCLOSURE: The unit is enclosed in a general purpose,
diecast housing. The cover is held in place with two tamper
resistant screws which require a special key for removal. A field
installable cover tamper switch is available as an option which may be
used to indicate unauthorized removal of the cover. See bulletin no.
5400775 for installation instructions of this switch.
INSTALLATION:
These devices may be mounted on horizontal or vertical pipe. On
horizontal pipe they should be installed on the top side of the pipe
where they will be accessible. The units should not be installed within
6" (15cm) of a fitting which changes the direction of the waterflow or
within 24" (60 cm) of a valve or drain.
Drain the system and drill a hole in the pipe using a circular saw in a
slow speed drill. The 2" (50mm) and 2 1/2" (65mm) devices require a
hole with a diameter of 1 1/4" + 1/8" - 1/16" (33mm ±2mm). All other
sizes require a hole with a diameter of 2" ±1/8" (50mm ±2mm).
Clean the inside pipe of all growth or other material for a distance equal to the pipe diameter on either side of the hole.
Roll the vane so that it may be inserted into the hole; do not bend or
crease it. Insert the vane so that the arrow on the saddle points in
the direction of the waterflow. Install the saddle strap and tighten
nuts alternately to an eventual 50 ft-lbs. (68 n-m) of torque (see Fig.
2). The vane must not rub the inside of the pipe or bind in any way.
Specifications subject to change without notice.